Specifications

ToolLink™ CDN466 DeviceNet™ to RS232 Gateways

CDN466
DeviceNet™ Interface
Data Rates 125K, 250K, 500K bits-per-second
Rotary switch or software selectable
MAC ID 0 to 63
Rotary switch or software selectable
Power Supply 11-28VDC, 200mA max.
Loss of Ground Full Protection Circuitry
Reverse Polarity -30VDC max.
CAN Signal Levels ISO 11898
Connector 5-pin male microconnector
Mode DeviceNet Group 2 Only Slave
I/O Messaging
Input Message Size
Output Message Size
Polled
4 to 68 bytes (4 overhead, 0 to 64 Rx Message data), software selectable
4 to 68 bytes (4 overhead, 0 to 64 Tx Message data), software selectable
Data Format Software selectable data word formats [high/low byte] or [low/high byte]
RS232 Interface
Data Rates 300, 600, 1200, 2400, 4800, 9600, 19200 bits-per-second
Rotary switch or software selectable
Parity Even, Odd, None. Software selectable. Automatic parity strip.
Data Bits 8 data bits with no parity, 7 data bits with parity
Flow Control RTS/CTS, xON/xOFF, None
Software selectable
Rx Message Framing Software selectable framing options -
Time Out: Inter-byte delay fixed at 4 byte-times
Fixed Length: 0 to 64 byte message lengths
Start/Stop Delimiters: 0 to 4 byte start-string and 0 to 4 byte stop-string
Handshake Optional Rx Message handshake to control data transfer rates over DeviceNet
Tx Buffer Size 128 bytes
Rx Buffer Size 128 bytes
Isolation 500V, between RS232 and DeviceNet interfaces
ESD Protection ±10 kV
Overload Protection ±30 V
Short Circuit Indefinite
Output Signal Levels ±7.9 V (typical)
Connector DB9 male
Operating Temperature 0 to 70°C
Storage Temperature -40 to 85°C
Dimensions 3.25 x 2.37 x 1.08 inches (82.6 x 60.2 x 27.4 mm)
0.5 inch (12.7 mm) mounting tabs
Mounting Holes 0.1875 inch (4.76 mm) diameter
DeviceNet™ Input Message Format
STS Status Byte
Bit 7 = Rx Buffer Empty
Bit 6 = Rx Buffer Overflow
Bit 5 = Rx Parity Error (automatically resets with new Rx message)
Bit 4 = Tx Buffer Empty
Bit 3 = Tx Buffer Overflow
RxC Receive Message Counter. Gateway increments RxC when new Rx Message is in Data field.
TxA Transmit Message Acknowledge. Gateway sets TxA equal to TxC after Tx Message is transmitted.
LENGTH Number of valid Rx Message bytes in the Data field.
DATA Fixed length field (0-64 bytes). Contains Rx Message bytes (left justified). Unused bytes are set to 0x00.
DeviceNet™ Output Message Format
CMD Command Byte
Bit 6 = Clear Rx Buffer (set bit to clear overflow error)
Bit 3 = Clear Tx Buffer (set bit to clear overflow error)
RxA Receive Message Acknowledge. Optional Rx handshake byte. Application sets RxA equal to RxC after processing last received message.
TxC Transmit Message Counter. Application increments TxC when new Tx Message is in Data field.
LENGTH Number of valid Tx Message bytes in Data field.
DATA Field length field (0-64 bytes). Contains Tx Message bytes (left justified).

Specifications are subject to change without notice.
Copyright MKS Instruments, Inc. unless noted otherwise.

Need help?

Contact an Applications Specialist by sending an email to MKS Instruments, or call 512-719-8000.