Compare Description Drawings, CAD & Specs Availability Price
Digital IO Module, 12 Source Inputs, 12 Source Outputs, 24 VDC Logic
$436
Digital IO Module, 12 Sink Inputs, 12 Sink Outputs, 24 VDC Logic
$436

Specifications

  • Type
    Digital Input/Output Module
  • Number of Inputs
    12
  • Input Type
    Sink or Source
  • Number of Outputs
    12
  • Power Consumption
    @ 200mA ≥ 24V_IO@ 2.5Amp, 24V_CORE@ 0.15Amp (per module) Assuming all DOs are loaded
  • Input Isolation
    2.5 kVrms
  • DI refresh rate
    10µs or 1ms
  • Debounce Filter
    Fixed to 4 cycles of DI Refresh Rate (10.8 µsec)
  • Logic Level
    24 VDC (8VDC - 30 VDC)
  • Maximum update rate
    25 µSec
  • Output Type
    Open collector sink/source
  • Protection
    ESD to IEC 1000-4-2 ±4kV contact, DC + 5% (each channel)
  • Pull Up/Down Value
    22K
  • Sink Input Logic Level
    24VDC ±5%
  • Sink Input Nominal Load Impedance
    6 kOhm
  • Sink Input Current, Maximum OFF
    2.25mA (10.7 V)
  • Sink Input Current, Minimum ON
    3.3mA (4.5 V)
  • Sink Input Current, Maximum ON
    4.7mA
  • Sink Output Maximum thermal current limit (ON)
    2A per bank of 6
  • Sink Output Maximum Available Current Sink (ON)
    200mA
  • Sink Output Maximum Leakage Current (OFF)
    0.1mA (output tied to 24v)
  • Sink Output Maximum Voltage Drop (ON)
    Maximum 1.1v @ 200mA
  • Sink Output Minimum Thermal Current Limit (ON)
    1A per bank of 6
  • Sink Output Maximum Inductive Load Energy, 1Hz Cycled
    60mJ
  • Source Input Logic level
    24v
  • Source Input High Voltage Range OFF
    12.8V (2.15 mA)
  • Source Input Low Voltage Range ON
    15V (2.5 mA)
  • Source Input Input Current, Maximum ON
    4.7mA
  • Source Input Nominal Load Impedance
    6 kOhm
  • Source Output Maximum Available Current Source (ON)
    200mA
  • Source Output Maximum Thermal Current Limit (ON)
    2A per bank of 6
  • Source Output Maximum Leakage Current (OFF)
    0.1mA (output tied to ground)
  • Source Output Minimum Thermal Current Limit (ON)
    1A per bank of 6
  • Source Output Output High Voltage
    Minimum 23.7V @ 200mA
  • Source Output Maximum Inductive Load Energy, 1Hz Cycled
    60mJ
  • Operating Temperature
    0 to 55°C, with 2°C upper limit reduction per 1000 ft above sea level
  • Storage Temperature
    -40°C to 85°C
  • Altitude
    0-10,000 ft above sea level
  • Humidity
    5-85% non-condensing
  • Dimensions
    35 x 125 x 92.3 mm (1.4 x 3.3 x 4.9 inches) (W x H x D)
  • Mounting
    DIN rail

Features

MKS Automation Platform

These modules are part of the MKS Automation Platform that provides a modular, scalable and configurable solution to meet your automation and control requirements. Designed to provide a complete automation solution to improve operational and productivity efficiencies, the Automation Platform enables faster implementations, provides lowest total cost of ownership, and improves utilization of existing tools and assets.

Need help?

Contact an Applications Specialist by sending us an email