Compare Description Drawings, CAD & Specs Availability Price
industrial automation analog input/output module
Pulse Width Modulating Slice Module
$395

Specifications

  • Type
    PWM Pulse Width Modulating Slice for Interfacing with Solid State Relays (SSR's)
  • Number of Inputs
    12
  • Input Type
    Sink or Source
  • Number of Outputs
    12
  • Power Consumption
    @ 200 mA ≥ 24 V_IO@ 2.5 Amp, 24 V_CORE@ 0.15 Amp Assuming all DOs are loaded
  • Control Method
    0 = Synchronized Random Fire SCR
    1 = Synchronized PWM zero cross
    2 = PWM zero cross / no AC, 50 Hz
    3 = PWM zero cross / no AC, 60 Hz
  • Input Isolation
    2.5 kVrms
  • DI refresh rate
    2.7 µSec
  • Debounce Filter
    Fixed to 4 cycles of DI Refresh Rate (10.8 µSec)
  • Logic Level
    24 VDC (8 - 30 VDC)
  • Maximum update rate
    25 µSec
  • Output Type
    Open collector sink/source
  • Output Resolution
    0.01% Full Scale power
  • Protection
    ESD to IEC 1000-4-2 ±4 kV contact, DC + 5% (each channel)
  • Pull Up/Down Value
    22 K
  • Sink Input Logic Level
    24 VDC ±5%
  • Sink Input Nominal Load Impedance
    6 k-ohm
  • Sink Input Current, Maximum OFF
    2.25 mA (10.7v )
  • Sink Input Current, Minimum ON
    3.3 mA (4.5v)
  • Sink Input Current, Maximum ON
    4.7 mA
  • Sink Output Maximum thermal current limit (ON)
    2 A per bank of 6
  • Sink Output Minimum Available Current Sink (ON)
    200 mA
  • Sink Output Maximum Leakage Current (OFF)
    0.1 mA (output tied to 24v)
  • Sink Output Minimum Thermal Current Limit (ON)
    1 A per bank of 6
  • Sink Output Maximum Inductive Load Energy, 1Hz Cycled
    60 mJ
  • Sink Output Output Low Voltage (ON)
    Max 1.1 V @ 200 mA
  • Source Input Logic level
    24 V
  • Source Input High Voltage Range OFF
    12.8 V (2.15mA)
  • Source Input Low Voltage Range ON
    15 V (2.5 mA)
  • Source Input Input Current, Maximum ON
    4.7 mA
  • Source Input Nominal Load Impedance
    6 kOhm
  • Source Output High Voltage
    Min 23.7 V @ 200mA
  • Source Output Maximum Thermal Current Limit (ON)
    2 A per bank of 6
  • Source Output Maximum Leakage Current (OFF)
    0.1 mA (output tied to Ground)
  • Source Output Minimum Thermal Current Limit (ON)
    1 A per bank of 6
  • Source Output Maximum Inductive Load Energy, 1Hz Cycled
    60 mJ
  • Source Output Minimum Available Current Source (ON)
    200 mA
  • Operational Environment Temperature
    0 to 55 °C, with 2 °C upper limit reduction per 1000 ft above sea level
  • Storage Temperature
    -40 to 85°C
  • Altitude
    up to 2000 meters
  • Humidity
    5 - 85% non-condensing
  • Dimensions
    35 x 125 x 92.3 mm (1.4 x 3.3 x 4.9 inches) (W x H x D)
  • Mounting
    DIN rail

Features

MKS Automation Platform

These modules are part of the MKS Automation Platform that provides a modular, scalable and configurable solution to meet your automation and control requirements. Designed to provide a complete automation solution to improve operational and productivity efficiencies, the Automation Platform enables faster implementations, provides lowest total cost of ownership, and improves utilization of existing tools and assets.